Dual setpoint controller that is easy to program. Controls submersible pumps in lift stations, and is designed to field calibrate the Birdcage Level Sensor.

Standard Features

  • Selectable pump alternation when used with two pumps to minimize pump wear. With alternation "On", a seal failure or over-temperature condition will force the non-failed pump to lead status and stop alternation.
  • Alarm light for seal failure when used with a sumersible pump that includes a moisture sensor.
  • Alarm light for overheating when used with a pump that includes a thermostat. Pump is removed from service and can be brought back online manually or automatically when pump has cooled down.
  • Runtime displayed by a front panel button.
  • 24 VDC power for level transmitter
  • 4 - 20 mA or voltage signal
  • Nonvolatile memory, no batteries
  • Test System function that simulates the process input to test programming or to insure the pumps are operating.
  • User-selectable security lock-out of programming and/or setpoints.

The Bulldog BD200 Pump Controller provides versatile level control in a standard 1/4 DIN package.

This controller is versatile, simple, and inexpensive making it the ideal instrument for controlling dual pump lifting stations. Setpoints for ON/OFF and HI/LO alarms are easily set on the front panel. These same buttons also Enable/Disable pump alternation. Selectable time delay up to 60 seconds on power up for pump two prevents both pumps from starting at the same time and a large current draw. Alarms for pump seal failure and motor windings overheating are indicated by lights on the front panel. The dial can also display a runtime clock for each pump. An isolated 4-20 mA retransmission is standard. The front face is rated NEMA-4X for outdoor panel mounting. The BD-200 is also available with RS-232 or RS-485 protocol for connectivity with SCADA systems.

Unit of Measure

Specifications

Input

N/A 2 (or 0) to 10 VDC selectable 4 (or 0) to 20 mADC

Input Impedance

N/A Current = 10 ohms, Voltage = 100 K ohms

Output Ratings

N/A Control Relays: SPDT, 10A @ 240 VAC resistive, 1/4 hp @ 120 VAC, 1/3 hp @ 240 VAC Alarm Relays: SPST, 3A @ 240 VAC resistive, 1/10 hp @ 120 VAC

Control Type

N/A Direct (pump in) acting On/Off, reverse (pump out)

Accuracy

N/A ± 0.25% of span ± 1 least significant digit

Display

N/A Two 4 digit, 7 segment, 14.2mm (0.56") high LED's

Resolution

N/A 1 count

Power Consumption

N/A 7.5 VA maximum

Electrical Supply

N/A 100 to 240 VAC nominal, +10% to 15%, 50 to 400 Hz single phase; 132 to 240 VDC +10% to 15%

Loop Powered Supply

N/A isolated +24 VDC @ 50mA, regulated

Operating Temperature Range

N/A -10 to 55 ºC-14 to 130 ºF

Storage Temperature Range

N/A -40 to 80 ºC-40 to 175 ºF

Humidity Range

N/A 0 to 90% up to 40ºC for non-condensing

Seal Failure (Moisture Sensor)

N/A Power: 2.5 VDC Resolution: 10K to 500K ohms in 10K ohm steps Search Current: 3 micro amps

Memory Backup

N/A Non-volatile memory, no batteries

Panel Cutout

N/A 92 x 92 mm3.622 x 3.622 in

Weight

N/A 454 g16 oz

Front Panel Rating

N/A IP66 (Type NEMA 4X)

Options

N/A

RS-232 or RS-485 with Mod bus protocol; Ethernet using TCP/IP

Accessories

N/A Weatherproof Enclosures, NEMA 4X

Agency Approvals

Agency Approvals

N/A